20 tubular-plate GEL models from 38 Ah to 3000 Ah — built for daily deep cycling and partial state-of-charge duty
If your battery is going to be discharged every day, you need more than a flat-plate AGM monobloc. The HGUG family is the tubular-plate GEL branch of the HGU platform — positive plates built from extruded tubular gauntlets filled with active material, electrolyte gelled with fumed silica, and a case designed for the deep-cycling reality of solar hybrid, microgrid and unstable-grid telecom sites. Twenty models from 38 Ah to 3000 Ah, in both 2 V cells and 12 V monoblocs, share the same float/equalise profile and the same cell hardware. Cycle life is rated at 1500 cycles at 50 % depth of discharge and over 5000 cycles at 20 % depth of discharge.
HGUG is the deep-cycle, tubular-plate GEL family within the HGU platform. Unlike flat-plate AGM, the positive plate is a tubular gauntlet — a non-woven polyester tube filled with lead dioxide pellets. This construction holds the active material together through thousands of charge-discharge cycles and gives HGUG its signature combination of long cycle life, low self-discharge and good recovery from deep discharge. The electrolyte is immobilised as a thixotropic GEL, so the cell is sealed and maintenance-free, but the GEL chemistry also resists stratification and thermal runaway better than AGM in daily-cycling service.
20 capacity steps from 38 Ah to 3000 Ah (C10 rate, 1.80 V/cell end voltage)
2 V cells and 12 V monoblocs on the same platform
Tubular positive plate, GEL electrolyte, sealed VRLA construction
Cycle life 1500 cycles at 50 % DoD, 2800 cycles at 40 % DoD, 5000+ cycles at 20 % DoD
Float design life 15 years at 25 °C
Operating temperature -20 °C to +45 °C
HGUG is engineered for sites that cycle the battery every day, not for sites that float it for years between rare discharge events:
Off-grid solar PV and solar hybrid systems
Microgrid buffer storage and remote-community power
Wind-hybrid and PV-wind-diesel hybrid plants
Telecom base stations on unstable grid or diesel-only sites
Traffic-light, motorway-control and railway-signalling DC supplies
Agricultural pumping and irrigation battery banks
Residential energy storage and small commercial PV-backup
Tubular gauntlets retain active material through thousands of cycles
Lower plate-growth and grid corrosion than flat-plate AGM at high DoD
Better recovery from accidental over-discharge
Immobilised GEL resists stratification in partial state-of-charge operation
Better thermal stability than AGM at high ambient temperature
Lower gas evolution — safe for cabinets with minimal ventilation
Wide operating window -20 °C to +45 °C without capacity loss
Same 2.23–2.27 V/cell float profile as the rest of the HGU platform
Cycle charge 2.30–2.40 V/cell for fast PV recharge
Compatible with common MPPT solar charge controllers
Tubular positive plate, GEL electrolyte, VRLA construction
Float voltage 2.23–2.27 V/cell at 25 °C, temperature-compensated -3 mV/°C/cell
Equalise / cycle charge 2.30–2.40 V/cell for up to 24 h
Operating temperature -20 °C to +45 °C (recommended 20–25 °C)
Self-discharge below 3 % per month at 25 °C
Container and cover ABS, flame-retardant to UL94 V-0 on request
Cycle life 1500 cycles at 50 % DoD, 2800 cycles at 40 % DoD, 5000+ cycles at 20 % DoD
Tubular GEL cells in 2 V and 12 V form factors; dimensions in millimetres
| Model | V | Ah (C10) | Length | Width | Height | Total H | Terminal | Case |
|---|---|---|---|---|---|---|---|---|
| HGUG12-38 | 12 | 38 | 197 | 166 | 168.5 | 168.5 | F16 | Black |
| HGUG12-65 | 12 | 65 | 348 | 167 | 177 | 177 | F16 | Black |
| HGUG12-90 | 12 | 90 | 306.5 | 168 | 211 | 217 | F16 | Black |
| HGUG12-100 | 12 | 100 | 330 | 173 | 213.5 | 220.5 | F20 | Black |
| HGUG12-120 | 12 | 120 | 408 | 177 | 224 | 224 | F20 | Black |
| HGUG12-150 | 12 | 150 | 483 | 170 | 239.5 | 239.5 | F20 | Black |
| HGUG12-200 | 12 | 200 | 522 | 239 | 218 | 224 | F20 | Black |
| HGUG12-250 | 12 | 250 | 522 | 268 | 220 | 226 | F20 | Black |
| HGUG2-100 | 2 | 100 | 171 | 72 | 205 | 211 | F20 | Grey |
| HGUG2-200 | 2 | 200 | 172 | 110 | 329 | 350 | F20 | Grey |
| HGUG2-300 | 2 | 300 | 171 | 150 | 329 | 351 | F20 | Grey |
| HGUG2-400 | 2 | 400 | 211 | 176 | 329 | 351 | F20 | Grey |
| HGUG2-500 | 2 | 500 | 242 | 172 | 329 | 351 | F20 | Grey |
| HGUG2-600 | 2 | 600 | 301 | 176 | 330 | 351 | F20 | Grey |
| HGUG2-800 | 2 | 800 | 410 | 176 | 330 | 345 | F20 | Grey |
| HGUG2-1000 | 2 | 1000 | 475 | 174 | 328 | 349 | F20 | Grey |
| HGUG2-1200 | 2 | 1200 | 475 | 174 | 328 | 349 | F20 | Grey |
| HGUG2-1500 | 2 | 1500 | 400 | 350 | 342 | 384 | F20 | Grey |
| HGUG2-2000 | 2 | 2000 | 491 | 351 | 342 | 368 | F20 | Grey |
| HGUG2-3000 | 2 | 3000 | 710 | 351 | 342 | 368 | F20 | Grey |
1500 cycles at 50 % depth of discharge at 25 °C
2800 cycles at 40 % depth of discharge at 25 °C
Over 5000 cycles at 20 % depth of discharge at 25 °C
Cycle life at elevated temperature derates by ~50 % per 8 °C above 25 °C
Partial state-of-charge (PSoC) operation does not accelerate capacity loss in HGUG, unlike flat-plate AGM
Float voltage: 2.23–2.27 V/cell at 25 °C (temperature-compensated -3 mV/°C/cell)
Equalise / cycle charge: 2.30–2.40 V/cell for up to 24 h
Operating temperature: -20 °C to +45 °C (recommended 20–25 °C)
Self-discharge: below 3 % per month at 25 °C
Storage re-charge interval: 6 months at 25 °C
Torque on terminal bolts: 6–8 N·m (F12/F16), 10–12 N·m (F20)
HG upsboss is the export brand of Shenzhen Shengpuwei Industrial Co., Ltd., a battery and UPS-systems manufacturer based in Shenzhen, China. We design, build and export VRLA, GEL, lead-carbon and LiFePO4 backup batteries for UPS, EPS, telecom, data-centre and renewable-storage operators in more than 60 countries. Every HGU-series battery ships with type-test reports, full BMS integration where applicable, and the CE / UL / IEC documentation you need for customs clearance and end-user acceptance.
All product specifications, images and documentation published on this page are the property of HG upsboss / Shenzhen Shengpuwei Industrial Co., Ltd. and are intended for legitimate procurement, engineering and integration use. Reproduction for counterfeit, misbranding or unauthorised resale is prohibited. Specification values are typical at 25 °C and may vary within published tolerances. Battery installations must comply with local electrical, ventilation and transport regulations.
HGUG uses a tubular positive plate — extruded polyester gauntlets filled with lead dioxide pellets — whereas flat-plate AGM uses a solid pasted plate. The tubular construction retains active material through many more charge-discharge cycles, which is why HGUG delivers 1500 cycles at 50 % DoD versus the ~500 cycles typical of flat-plate AGM at the same depth.
Yes. HGUG floats at the same 2.23–2.27 V/cell as the rest of the HGU platform and can sit in float standby for years. Many operators choose HGUG specifically because it gives them both the float standby rating they need today and the cycling headroom they may need tomorrow if the site conditions change.
Yes — this is exactly what HGUG is built for. In a solar-hybrid microgrid that never reaches 100 % state-of-charge, HGUG retains more capacity over time than flat-plate AGM. For extreme PSoC duty (micro-cycles several times a day), consider the HGUC lead-carbon family instead.
Yes — set the MPPT absorption stage to 2.30–2.40 V/cell (13.8–14.4 V for a 12 V monobloc) for up to 24 hours, then drop to float at 2.23–2.27 V/cell (13.4–13.6 V for 12 V). HGUG tolerates the typical MPPT sweep profile without harm.
In a daily 50 % depth-of-discharge cycle at 25 °C, expect 1500 cycles (about 4 years of service). In a 20 % daily cycle, expect 5000+ cycles (about 13 years). For sites warmer than 25 °C, derate cycle life by ~50 % per 8 °C.
Both use the same tubular plate and GEL chemistry. The 12 V monoblocs are convenient for smaller battery banks (under 500 Ah) where the DC bus voltage is 12 V or 24 V. The 2 V cells are the building block for 48 V telecom plants and large solar battery banks from 100 Ah to 3000 Ah per cell.
No — HGUG is sealed VRLA with immobilised GEL electrolyte. There is no access port for topping-up and no scheduled maintenance other than torque checks and visual inspection.
No — HGUG is a lead-acid GEL cell and must be charged with a lead-acid charge profile. Using a lithium-ion charger on HGUG will undercharge the cell and permanently reduce capacity. Always use a lead-acid-compatible charger with the correct float, absorption and equalise settings.